Info: Your browser does not accept cookies. To put products into your cart and purchase them you need to enable cookies.
Encoder H21A1FLUKE117
 View Full-Size Image
|
Fluke 336
|
Price per Unit (Unidad):
Call for Pricing
|
|
| Ask a question about this product |
| Specifications | | Voltage DC | | Range: | 0 - 600.0 V | | Accuracy: | 1% ± 5 counts |
| | Voltage AC | | Fluke 333/334 | | | Range: | 0 - 600.0 V | | Accuracy: | 1% ± 5 counts (50/60 Hz) | | AC Response: | Averaging | | Fluke 335 | | | | | | Range: | 0 - 600.0 V | | Accuracy: | 1% ± 5 counts (50/60 Hz) | | AC Response: | True-rms | | | | | Fluke 336/337 | | | Range: | 0 - 600.0 V | | Accuracy: | 1% ± 5 counts (20-100 Hz), 6% ± 5 counts (100-400 Hz) | | AC Response: | True-rms |
| | Current DC | | Fluke 336 | | | Range: | 0 - 600.0 A | | Accuracy: | 2% ± 5 counts | | | | | Fluke 337 | | | Range: | 0 - 999.9 A | | Accuracy: | 2% ± 5 counts |
| | Current AC | | Fluke 333 | | | Range: | 0 - 400.0 A | | Accuracy: | 2% ± 5 counts (50/60 Hz) | | AC Response: | Averaging | | | | | Fluke 334 | | | Range: | 0 - 600.0 A | | Accuracy: | 2% ± 5 counts (50/60 Hz) | | AC Response | Averaging | | | | | Fluke 335 | | | Range: | 0 - 600.0 A | | Accuracy: | 2% ± 5 counts (50/60 Hz) | | Crest Factor(50/60 Hz): | 2.4 @ 500A, 2.0 @ 600A, add 2% for CF>2 | | AC Response: | True-rms | | | | | Fluke 336 | | | Range: | 0 - 600.0 A | | Accuracy: | 2% ± 5 counts (10-100 Hz), 6% ± 5 counts (100 - 400 Hz) | | Crest Factor(50/60 Hz): | 3 @ 500A, 2.5 @ 600A, add 2% for CF>2 | | AC Response: | True-rms | | | | | Fluke 337 | | | Range: | 0 - 999.9 A | | Accuracy: | 2% ± 5 counts (10-100 Hz), 6% ± 5 counts (100 - 400 Hz) | | Crest Factor(50/60 Hz): | 3 @ 500A, 2.5 @ 600A, 1.42@1000 A, add 2% for CF>2 | | AC Response: | True-rms |
| | Resistance | | Fluke 333 | | | Range: | 0 - 600.0 ? | | Accuracy: | 1.5% ± 5 counts | | | | | Fluke 334/335/336/337 | | | Range: | 0 - 600.0 ?, 600 - 6000 ? | | Accuracy: | 1.5% ± 5 counts |
| | Frequency | | Fluke 337 | | | Range: | 5 - 400Hz | | Accuracy: | 0.5% ± 5 counts | | Trigger Level: | 10-100 Hz >= 5A, 5-10 Hz, 100-400 Hz >=10A |
| | Inrush Current | | Fluke 334/335/336/337 | | | Integration Time: | 100 ms |
| | Continuity | | | MIN/MAX | |
| Environmental Specifications | | Operating Temperature | | | -10 °C to +50 °C, -14 °F to 122 °F |
| | Storage Temperature | | | -40ºC to +60ºC, -22 °F to 140 °F |
| | Operating Altitude | | | 2,500 meters max, 6,500 ft max |
| | Temperature De-rating | | | Add 0.1 x specified accuracy for each ºC above 28ºC or below 18ºC (above 82.4°F or below 64.4°F) |
|
| Safety Specifications | | Safety Rating | | | IEC 1010-2-032, 600V CAT III |
|
| Mechanical & General Specifications | | Size | | Fluke 333/334/335 | | | | 240mm x 80mm x 40mm (9.375" x 3.125" x 1.625") | | | - | | Fluke 336/337 | | | | 250mm x 80mm x 40mm (9.875" x 3.125" x 1.625") |
| | Weight | | | Warranty | | | Battery Life | | | Alkaline approximately 150 hours continuous | | | Automatic low battery indicator |
| | Backlight | | | Display Hold | |
|
|
|
|
Customer Reviews: